Power rating 300 W
Efficiency 81 % Min.
Rated input voltage 100 to 240 VAC
Allowable input voltage variable range 85 to 264 VAC
Frequency 50/60 Hz(47 to 63 Hz Single-phase)
Rated input curren 4.3A Max. (At 100 VAC input)
2.2A Max. (At 200 VAC input)
Power factor 0.98 Min. (At 100 VAC input)
0.94 Min. (At 200 VAC input)
Leakage current 0.4 mA Max. (At 100 VAC input)
0.75 mA Max. (At 200 VAC input)
Inrush current 20 A Max. (At 100 VAC input (For cold start at 25 CEL))
40 A Max. (At 200 VAC input (For cold start at 25 CEL))
Output voltage 24 VDC
Output voltage variable range -20 to +20 % (With V. ADJ)
(The output voltage may increase beyond the allowable voltage range (up to +20% of the rated voltage) depending on the operation of the output voltage adjuster (V.ADJ). When adjusting the output voltage, check the output voltage of the Power Supply and be sure that the load is not damaged.)
Ripple 1.25%(p-p) Max.
Static input variation influence 0.4% Max. At 85 to 264 VAC input, 100% load
Static load variation influence 0.6% Max. At rated input, 0 to 100% load
Ambient temperature variation influence 0.02 %/CEL Max. (At rated input/output voltage)
Rated output current 14 A / 16.5 A (Peak current at 200 VAC)
Start up time 1000 ms Max. (At rated input/output voltage)
Hold time 20ms TYP.
Overload protection 120% to 160% of the rated output current
Inverted L voltage drop, Automatic reset
Overvoltage protection Operated at 125 to 145 % of the rated output voltage, Shut-off
Resetting: Reset the power by turning it back (OFF time: at least 1 min)
Overheat protection Yes
Resetting: Reset the power by turning it back (OFF time: at least 3 min) Alternatively, turn OFF the remote control signal and then turn it back ON again
Maintenance forecast monitor output No
Total run time monitor output No
Undervoltage alarm output No
Power failure alarm indication Yes (color: red)
Power failure alarm output Yes (open collector output), 30 VDC Max., 50 mA Max.
Parallel operation Yes (Up to 2 Power Supplies)
Series operation Yes (Up to 2 Power Supplies with external diode)
Remote sensing function Yes
Dielectric strength Between all inputs and all outputs: 3 kVAC for 1 min (Detection current: 20 mA)
Between all inputs and PE terminals: 2 kVAC for 1 min (Detection current: 20 mA)
Between all outputs and PE terminals: 500 VAC for 1 min (Detection current: 100 mA)
Between all outputs and RC terminals: 100 VAC for 1 min (Detection current: 100 mA)
Between all outputs and PF terminals: 500 VAC for 1 min (Detection current: 20 mA)
Insulation resistance Between all outputs and all inputs/ PE terminals: 100 MOhm Min. (at 500 VDC)
Vibration resistance 10 to 55 Hz, 0.375 mm single amplitude in each 3 directions for 2 hours
Shock resistance 150 m/s**2, in each 6 directions 3 times
Output indicator Yes (color: green)
Heat radiation Forced air-cooling
Construction Covered type
Mounting type Bottom-mounting type
Attachment Instruction manual