10 kA Icu conforming to IEC 60947-2 - 125...180 V DC
10 kA Icu conforming to EN 60947-2 - 125...180 V DC
6000 A Icn conforming to IEC 60898-1 - 400 V AC 50/60 Hz
6000 A Icn conforming to EN 60898-1 - 400 V AC 50/60 Hz
6 kA Icu conforming to IEC 60947-2 - 440 V AC 50/60 Hz
6 kA Icu conforming to EN 60947-2 - 440 V AC 50/60 Hz
36 kA Icu conforming to IEC 60947-2 - 12...60 V AC 50/60 Hz
36 kA Icu conforming to IEC 60947-2 - 100...130 V AC 50/60 Hz
36 kA Icu conforming to EN 60947-2 - 12...60 V AC 50/60 Hz
36 kA Icu conforming to EN 60947-2 - 100...130 V AC 50/60 Hz
20 kA Icu conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz
20 kA Icu conforming to EN 60947-2 - 220...240 V AC 50/60 Hz
10 kA Icu conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz
10 kA Icu conforming to EN 60947-2 - 380...415 V AC 50/60 Hz
Utilisation category
Category A conforming to IEC 60947-2
Category A conforming to EN 60947-2
Suitability for isolation
Yes conforming to IEC 60947-2
Yes conforming to IEC 60898-1
Yes conforming to EN 60947-2
Yes conforming to EN 60898-1
Complementary
Network frequency
50/60 Hz
[Ue] rated operational voltage
12...144 V DC
440 V AC 50/60 Hz
400 V AC 50/60 Hz
380...415 V AC 50/60 Hz
220...240 V AC 50/60 Hz
12...60 V AC 50/60 Hz
100...130 V AC 50/60 Hz
Magnetic tripping limit
8 x In +/- 20 %
[Ics] rated service breaking capacity
4.5 kA 75 % x Icu conforming to IEC 60947-2 - 440 V AC 50/60 Hz
7.5 kA 75 % x Icu conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz
15 kA 75 % x Icu conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz
27 kA 75 % x Icu conforming to IEC 60947-2 - 100...130 V AC 50/60 Hz
4.5 kA 75 % x Icu conforming to EN 60947-2 - 440 V AC 50/60 Hz
7.5 kA 75 % x Icu conforming to EN 60947-2 - 380...415 V AC 50/60 Hz
15 kA 75 % x Icu conforming to EN 60947-2 - 220...240 V AC 50/60 Hz
27 kA 75 % x Icu conforming to EN 60947-2 - 100...130 V AC 50/60 Hz
6 kA 100 % x Icu conforming to IEC 60947-2 - 12...144 V DC
6 kA 100 % x Icu conforming to EN 60947-2 - 12...144 V DC
27 kA 75 % x Icu conforming to IEC 60947-2 - 12...60 V AC 50/60 Hz
27 kA 75 % x Icu conforming to EN 60947-2 - 12...60 V AC 50/60 Hz
Limitation class
3 conforming to IEC 60898-1
3 conforming to EN 60898-1
[Ui] rated insulation voltage
500 V AC 50/60 Hz conforming to IEC 60947-2
500 V AC 50/60 Hz conforming to EN 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-2
6 kV conforming to EN 60947-2
Contact position indicator
Yes
Control type
Toggle
Local signalling
Trip indicator
Mounting mode
Fixed
Mounting support
DIN rail
Comb busbar distribution block compatibility
YES top or bottom
9 mm pitches
6
Height
85 mm
Width
54 mm
Depth
78.5 mm
Product weight
0.375 kg
Colour
White
Mechanical durability
20000 cycles
Electrical durability
10000 cycles
Connections - terminals
Single terminal, top or bottom flexible wire(s) 1...25 mm² max
Single terminal, top or bottom rigid wire(s) 1...35 mm² max
Wire stripping length
14 mm top or bottom
Tightening torque
3.5 N.m top or bottom
Earth-leakage protection
Separate block
Environment
Standards
EN 60898-1
EN 60947-2
IEC 60898-1
IEC 60947-2
IP degree of protection
IP20 conforming to EN 60529
IP20 conforming to IEC 60529
Pollution degree
3 conforming to IEC 60947-2
3 conforming to EN 60947-2