Power supply:
Direct current
Working voltage:
8.2 Vdc (1Kohm)
Switching distance (mm):
3
Output type:
Namur
Hysteresis (%Sn):
1 ÷ 10
Max. switching frequency:
2000 Hz
Repeatability (%Sn):
<= 3
Current absorption at 8.2V:
Target detected <= 1 mA - Target not detected >= 3 mA
Led indicator:
Present
Operating temperature limits:
-25 ÷ +60 °C
Storage temperature limits:
-30 ÷ +70 °C
IP rating:
IP 67
Housing material:
Nickelled brass
Cable type:
2x0.25 mm² PVC
Weight:
140 g
Mechanical characteristics:
M14x1
Connection type:
Cable 5 m
Explosive atmosphere type:
Mixture Air/gas and/or Air/Dust
Equipment category:
1G / 1D
Installation area:
Gas: Zone 0, Zone 1 and Zone 2 - Dust: Zone 20, Zone 21 and Zone22
Protection method:
Intrinsically safe
Marking:
Gas: II 1G Ex ia IIC T6 Ga - Dust: II 1D Ex ia IIIC T85°C Da -25< Ta
Safety information:
Connection to certified intrinsically safe circuits only with the following values : Uo <= 17 V ,
Conforming standard:
EN60079-0, EN60079-11, EN60079-26 and EN60947-5-6
EC-tipe examination certificate - ATEX:
IMQ 13 ATEX 019
Certificate of conformity (CoC) - IECEx:
IECEx IMQ 13.0012X