Power rating
30 W
Efficiency
85% TYP. (at 100 VAC input)
86% TYP. (at 200 VAC input)
Rated input voltage
100 to 240 VAC
Allowable input voltage variable range
85 to 264 VAC
80 to 370 VDC
Note at DC input
The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Frequency
50/60 Hz (47 to 450 Hz)
Rated input curren
0.66 A TYP. (at 100 VAC input)
0.4 A TYP. (at 200 VAC input)
Leakage current
0.5 mA max. (at 100 VAC input)
1.0 mA max. (at 200 VAC input)
Inrush current
14 A TYP. (at 100 VAC input)
28 A TYP. (at 200 VAC input)
Output voltage
24 VDC
Output voltage variable range
-10 to +15% (With V. ADJ)
Ripple
150 mV max. (Under the rated I/O conditions.)
Static input variation influence
0.5% max. at 85 to 264 VAC input, 100% load
Static load variation influence
1.5% max. at rated input, 0 to 100% load
Ambient temperature variation influence
0.05 %/℃ max.
Rated output current
1.3 A
Start up time
560 ms TYP. (at 100 VAC input)
400 ms TYP. (at 200 VAC input)
Hold time
31 ms TYP. (at 100 VAC input)
140 ms TYP. (at 200 VAC input)
Overload protection
105% to 160% of the rated output current, Inverted L voltage drop, Intermittent operation, Automatic reset
Overvoltage protection
Operated at 130% min. of the rated output voltage, Shut-off
Resetting: Reset the power by turning it back (OFF time: at least 3 min)
Overheat protection
No
Undervoltage alarm output
No
Power failure alarm output
No
Parallel operation
No (However, backup operation is possible; external diodes required.)
Series operation
Yes (Up to 2 Power Supplies with external diode)
Dielectric strength
Between all inputs and all outputs: 3 kVAC for 1 min (Detection current: 20 mA)
Between all inputs and PE terminals: 2 kVAC for 1 min (Detection current: 20 mA)
Between all outputs and PE terminals: 1 kVAC for 1 min (Detection current: 20 mA)
Insulation resistance
Between all outputs and all inputs/ PE terminals: 100 MΩ min. (at 500 VDC)
Vibration resistance
10 to 55 Hz, 0.375 mm single amplitude in each 3 directions for 2 hours
Shock resistance
150 m/s**2, in each 6 directions 3 times
Output indicator
Yes (color: green)
Heat radiation
Natural air-cooling
Construction
Covered type
Structure
Terminal blocks
Terminal type
Screw terminal
Attachment
Terminal block cover
Weight (Main)
Approx. 180 g