Function
1 Stage Preset Counter
Preset stages
1stages
Rated supply voltage
100 to 240 VAC 50/60 Hz
Operating voltage range
85% to 110% of the rated power supply voltage
Power consumption
Approx. 10 VA (at 100 VAC)
External power supply
12 VDC ±10% 80 mA (permissible ripple: 5%(p-p) Max.)
Counter (Count range)
0~9999
Counter (Max. counting speed)
30 Hz/5 kHz (switching) (Minimum counting input signal width: 16.7 ms (ON/OFF ratio: 1:1)/0.1 ms (ON/OFF ratio: 1:1))
Counter (Input mode)
Increment or decrement (switchable)
Counter (Output modes)
N / F / C / R / K / P / Q
Counter One-shot time)
0.1 to 1 s variable
Counter (Reset system)
External, manual, automatic and power reset (when set the SW3 for No memory backup)
Input signal
CP1 / CP2 / Reset
Input method
Voltage input
No-voltage input (Contact input)
Use a contact which can adequately switch 2.5 mA at 12 V.
Voltage input
Hight level: 5 to 30 VDC
Low level: 0 to 2 VDC
Input resistance: 4.7 kΩ
Minimum input signal width
External reset: 20 ms
Manual reset: 20 ms
Automatic reset: 100 to 1000 ms (C, R, P and Q mode)
Control output (Contact output)
SPDT
Switching capacity: 3 A at 250 VAC/30 VDC, resistive load (cos phi=1)
Minimum applicable load: 10 mA at 5 VDC (failure level:P reference value)
Control output (Solid-state output)
Output type: Transistor output (NPN open collector)
Output resistance: 1.5 kΩ
Switching capacity: 30 VDC max., 100 mA max.
Display method
7-segment LED
Digits
4digits
Character height
Count value: 10 mm (Red)
Zero suppression: Not provided
Prescaling function
Not provided
Key protection
Not provided
Teaching function
Not provided
Batch counting function
Not provided
Communications
Not provided
Memory backup
Non-volatile memory (Number of rewite: 1,000,000 operations min.)
Surrounding air temperature
Operating: -10 to 55 ℃
Storage: -25 to 65 ℃
Ambient humidity
Operating: 35 to 85%
Storage: 35 to 85%
Insulation resistance
100 MΩ min. (at 500 VDC)
Between current carrying terminals and exposed non-current carrying metal parts / Between non-continuous contacts
Dielectric withstand voltage
Between current carrying terminals and exposed non-current carrying metal parts:2000 VAC 50/60 Hz for 1 min
Between non-continuous contacts:750 VAC 50/60 Hz for 1 min
Impulse withstand voltage
Between power terminals:6.0 kV
Between current carrying terminals and exposed non-current carrying metal parts:6.0 kV
Noise immunity
Between power terminals:±2k V
Between input terminals:±500 V
Square-wave noise by noise simulator (Pulse width: 100 ns/1 µs, 1-ns rise)
Static immunity
±8 kV (malfunction), ±15 kV (destruction)
Vibration resistance (Destruction)
10 to 55 Hz, 0.375-mm single amplitude each in 3 directions for 2 h
Vibration resistance (Malfunction)
10 to 55 Hz, 0.25-mm single amplitude each in 3 directions for 10 min
Shock resistance (Destruction)
300 m/s**2, 3 times each in 6 directions (3 axes)
Shock resistance (Malfunction)
100 m/s**2, 2 times each in 6 directions
Mechanical life expectancy
10,000,000 operations min.
Electrical life expectancy
100,000 operations min. (3 A at 250 VAC, resistive load)
Degree of protection
Case front: JEM IP30
Mounting method
Flush mounting
External connection method
Screw terminal
Case color
Light gray (Munsell 5Y7/1)
Accessories
Mounting bracket
Weight
Approx. 360 g