power quality analysis
Up to the 15th harmonic
device application
Power monitoring
type of measurement
Energy
Active and reactive power
Voltage
Current
Frequency
Power factor
supply voltage
100...415 V AC (45...65 Hz)
125...250 V DC
network frequency
50 Hz
60 Hz
[In] rated current
1 A
5 A
type of network
1P + N
3P
3P + N
power consumption in VA
<= 10 VA at 415 V
ride-through time
80 ms 120 V AC typical
100 ms 230 V AC typical
100 ms 415 V AC typical
display type
Backlit LCD
display resolution
128 x 128 pixels
sampling rate
64 samples/cycle
measurement current
10...9000 mA
analogue input type
Current (impedance 0.3 mOhm)
Voltage (impedance 5 MOhm)
measurement voltage
35...690 V AC 45...65 Hz between phases
20...400 V AC 45...65 Hz between phase and neutral
frequency measurement range
45...65 Hz
number of inputs
0
measurement accuracy
+/- 0.5 % active energy
+/- 2 % reactive energy
+/- 0.5 % active power
+/- 0.5 % apparent power
+/- 0.05 % frequency
+/- 0.005 % power factor
+/- 0.5 % current
+/- 0.5 % voltage
accuracy class
Class 0.5S (active energy according to IEC 62053-22)
number of outputs
1 digital
communication port protocol
Modbus RTU and ASCII 2 wires, : 9.6, 19.2 and 38.4 kbauds, even/odd or none, insulation: 2500 V
JBUS
communication port support
RS485
data recording
Min/max of instantaneous values
Time stamping
connections - terminals
Voltage circuit: 4 screw terminal block
Control circuit: 2 screw terminal block
Current transformer: 6 screw terminal block
Input/output circuit: 6 screw terminal block
RS485 link: 4 screw terminal block
mounting mode
Flush-mounted
mounting support
Framework
standards
IEC 60529
IEC 61557-12
IEC 62053-22
EN 50470-1
EN 50470-3
UL 61010-1
IEC 62053-24
product certifications
CE conforming to IEC 61010-1
CULus conforming to UL 61010-1
MID conforming to EN 50470-1
MID conforming to EN 50470-3
width
96 mm
depth
72 mm
height
96 mm
product weight
380 g